Product Nr.: 04-1200-05
A cluster of red LED's for permanent fault and one green LED for transient fault. In addition a single LED will give indication on low battery status. High visibility.
LineTroll 110Eμ continuously monitors the line voltage and phase current, the sources of information it needs to operate. The unit is fully self-contained, no external transformers or connections is required. During normal line conditions, LineTroll 110Eμ remains extinguished.
The indicator is looking for a specific sequence of line conditions to happen before it starts flashing. The general sequence is as follows:
A. The line should be energised (voltage or current present) for a minimum of 5 seconds.
B. Di/Dt : The line current should increase rapidly by the amount of a user set value (the step level). Treshold, the line current exceeding a present current level.
C. The line should be de-energised. (Voltage or current not present).
The user may program the criteria for operation to suit his local requirements by manipulating a bank of micro-switches inside the indicator.
Note: Voltage or current as start and stop criteria is user programmable.
Short circuit and Earth fault indication for overhead lines.
System voltage: 6-69 [kV] medium voltage networks.
Grounding system: Isolated, resistor and solidly grounded.
Sensitivity Di/Dt, 50[Hz]: 6, 12, 25, 60 or 120 [A] *
Sensitivity Treshold, 50[Hz]: 250, 500, 750 or 1000 [A] *
Duration: > 60 [ms] (20[ms] on request)
Inrush blocking: 5 sec.
CB-Tripping: Within 5 sec.
Automatic: Re-energised line (Voltage or current, programmable)
Timer: 2, 6, 12 or 24 hours *
Manual: By magnet / Mounting reset tool
Note*: All tresholds, timers etc. are selectable and programmable by dip-switches.
Indication:Permanent faults: 4 red and 1 green LED.
Transient faults: 1 green LED.
Intensity: > 12 lumens for permanent faults.
Visibility:
Day: 250[m]
Night: 2 [km]
Direction: 360 degrees
Flashing frequency: f = 0.2 [Hz], after 12 h reduced to f=0.1 [Hz].
Low battery indication: 1 LED (f=0.1 [Hz]).
1 Lithium cell: D-size total capacity 16.5 [Ah]
Battery change: every 1500 flash hours, normal conditions every 7-8 years.
Hot-stick: Live line mounting with KBN-3 mounting tool.
Conductor size: 5-24 [mm]
Temperature: - 40 to +85 [C]
Housing: Polycarbonate, UV stabilized.
Dimension: 202 x 54 [mm] (with box, 235x65x85)
Weight: 460 [g] (Box and battery included)
Degree of protection: IP54