Skip to contentTechnical specifications
- Application
- Communication module for earth fault and short circuit fault indicators for underground cable networks.
- Communication
- Built in GSM module. GPRS connection with SMS as backup-channel.
- GSM module 4G with 2G fallback.
- Connects to NetTroll 4.1 TCP, or NetTroll SCADA Gateway for SCADA connection on DNP3 or IEC60870-5-104.
- Functions
- The GSM module is normally switched OFF when no alarms to transmit.
- Sets up a GPRS connection to transfer alarms upon changes on one of the digital or analog inputs. Active Low/Active High is configurable. Activation time of the digital inputs configurable in the range 100ms to 2.5s.
- Sends Heartbeat message in configurable interval.
- Possible to set up SMS recipients if GPRS fails or as a copy.
- Polls the GSM network regular to check for incoming messages.
- Three individual recipient telephone numbers for SMS, or IP address for mail GPRS connection point.
- Test/reset push-buttons on the front panel.
- Inputs
- 4 general digital inputs, opto isolated inputs is optional.
- 2 general 12 bits analog inputs (4-20mA)
- Relay output
- Rated current: 5A
- Rated voltage / max. switching voltage AC 240/400 VAC
- Maximum breaking capacity AC 1250 VA
- Power Supply
- 2 x 3,6V Lithium batteries KBB-20 (replaceable)
- External DC 9-30VDC, 1A max and 1x KBB-20 battery
- Operational lifetime > 10 years (Dependent on activity and heartbeat intervals etc.)
- Operational Temp Range
- -25ºC to +80ºC, 90% humidity, non-condensing.
- Housing
- Poly carbonate, UV stabilized
- Weight
- 0.62kg, including packaging