Linetroll
Linetroll 110Eμ
Linetroll 110Eμ is a line mounted indicator for detection of PtG and PtP faults in overhead line networks.
- Single distribution systems
- Distribution systems with earth-wire
- Multiple distribution systems

About Linetroll 110Eμ
The indicator is powered by replaceable long-life lithium batteries which have a life expectancy of 10-15 years. It provides a 360 degree visibility for indication both for transient faults and permanent faults.
Technical specifications
- Application
- Short circuit and Earth fault indication for overhead lines.
- System Voltage: MV voltage network (6-69kV)
- Grounding system: Isolated, resistor and solidly grounded
- Frequency: 50Hz / 60 Hz
- Fault-detection
- Sensitivity Di/Dt (50Hz): 6, 12, 25, 60 or 120A*
- Sensitivity threshold (50Hz): 250, 500, 750 or 1000A*
- Duration: > 60ms (Any value upon request)
- Inrush-blocking: 5 sec
- CB-tripping: Within 5 sec
- Reset
- Automatic: Re-energized line (Voltage or current, programmable)
- Timer: 2, 6, 12, or 24 hours*
- Manual: By magnet/Mounting-reset tool
- Note
- * All threshold, timers etc. are selectable and programmable by microswitches.
- Indication
- 3 high intensity LED’s
- Intensity: < 40 lumens for Permanent faults
- Permanent faults: Ultra Bright Red Strobe Flash
- Transient faults: 1 green LED (f = 0,2Hz)
- Low battery: 1 LED (f = 0,1Hz) IF Tot. time >5year OR <20% of tot capacity (16,5Ah) left
- Visibility day/night/dir.
- <500m/2km / 360°
- Power supply
- 1 Lithium Cell, D size tot capacity: 16,5 Ah
- Battery change: Every 1500 flash hours, normally every 10 years, 15 year shelf life.
- Mounting
- Hot-stick: Live-line mounting with Grip-All Clamp hot-stick or KBN-4 mounting tool.
- Conductor size: 5-36 mm
- Temperature range
- -40° to +70°C
- Housing
- Material: Polycarbonate, UV stabilized
- Dimension: 202 x 54mm (with box 235 x 65 x 85)
- Weight: 345g incl. battery
- Protection
- Ingress: EN 60529 IP 64
- Mechanical Impact: EN 62262 IK 09 (10J)